260613 · DEV3896 East Lake Pkwy C-Store — Water & Sewer
HCWA Digital As-built CAD Standards for Consultants, Rev 1.6 (Nov 1, 2023)
Sources
- Live drawing sweep (ticket C3D-QACHECK, read-only)
- Plotted sheet CSTORE WATER ABS-260612_SHEET-SHEET-17x11.pdf
- REDLINE/As-built CAD Standards for Consultants.pdf
▾ General requirements 9
- ✓CAD/DWG formatCivil 3D 2025
- ✓US Survey FeetINSUNITS = Feet (verified)
- ✓NAD83 GA West Zone state plane, geo-referencedE≈2,296,xxx / N≈1,280,xxx consistent with GA West; sheet notes 'GA SPW (US FT)'
- !Two reference survey markers (pins) with x,y,z tied to the Henry County GPS monument network0 entities on HORIZONTAL_AND_VERTICAL_CONTROL_POINT. All 140 COGO points searched — no IPF/IPS/rebar/monument/control/benchmark code exists. Not on the as-built PDF either. Needs field monument ties; cannot be drafted.
- ✓All features surveyed after construction140 COGO points from field survey
- ✓Point features shot directly (hydrants, valves, manholes, cleanouts)FH ×2, WV ×3, SSMH ×10, grease traps ×4
- ✓Line features — pipe endpoints & bends >45°12 sewer tangents, 4 water lines
- ~Polygon features — easements, R/W, lot lines, project boundaryeasements done; R/W, lot lines and project boundary still empty
- –Final plats with address + lot number inside each closed lotcommercial site, not a subdivision plat
▾ Layers 12
- ✓Layer names exactly as the HCWA tableall 70 HCWA layers created with exact names
- ✓Layers contain only their described featuressewer/water/hydrant split by feature type
- ✓No near-duplicate layer namesno WATER_LINE / WATER_LINES collisions
- ✓Text NOT on the feature's own layerSEWER_MANHOLE_TEXT vs SEWER_LINE_TEXT correctly split
- ○ROAD_RIGHT-OF-WAY populatedempty — East Lake Pkwy 150' R/W, Springdale Rd 80' R/W per as-built. Only 1 R/W point shot.
- ○PROJECT_BOUNDARY populatedempty — required closed polygon
- ○PROPERTY_LINE populatedempty
- ○ADDRESS_TEXT populatedempty — and the sheet says 5000 East Lake Pkwy while the folder says 5030. Confirm which.
- ○WATER_METER populatedempty — 6" fire + 2" domestic meters are in vault 1118–1121
- ○SEWER_TAP populatedempty — 4"SL / 6"SL laterals shown on the as-built
- –LOT_NUMBER_TEXTcommercial, no lot number
- –SEWER_END_OF_LINEno sewer stubbed for future
▾ Sewer features 5
- ~Drawn uphill node → downhill nodeinverts fall correctly (1105 I721.54 → 1095 I718.11 → 1094 I717.43 → 1099 I713.74 → 100 I712.37) but drawn direction not programmatically verified — check in CAD
- ✓Single line per tangent, never more than one0 multi-tangent polylines; 12 discrete Line tangents
- ~Tangents snapped at exact manhole centre, no gaps16 of 24 endpoints exact (0.00 ft). The main run 1106→1105→1103→1095→1099→100 is perfect. The 8 loose ends belong to 3 tangents that are not sewer mains (10–66 ft from any manhole; 2 touch easement vertices).
- ✓Manholes symbolised consistently, circle centred on tangent endpoints10 circles r=2.00 centred. 2 missing manholes (#101, #102) were found and added.
- ○Sewer taps snapped to the tangent, accurately placedSEWER_TAP empty; laterals not yet drawn
▾ Water features 7
- ~Straight pipes = exactly 2 points, node to node4 water lines; 5-vertex and 4-vertex runs exist and may need splitting unless they contain genuine bends
- ✓Polylines only where the line bendsbends present on the alignment
- ✓Hydrants in true surveyed locationFH 1115, 1131 at field coordinates
- ✓Hydrants connected to main via a valved fire hydrant line1115 FH + 1116 WV are 1.2 ft apart; 1130 WV + 1131 FH are 1.8 ft. FHA noted at 1130/1131.
- ~All lines continuous, endpoints snapped at nodesnot programmatically verified — check in CAD
- ✓End-of-line caps for permanently capped linesWATER_END_CAP ×1 — the 6" capped PVC stub (pt 1132)
- ○Water meters on WATER_METERempty; 6" fire + 2" dom meters exist in vault 1118–1121
▾ Easements 2
- ✓All easements shown on their layerSEWER_EASEMENT — the 20' S.S.E.
- ~Easements must be closed polygons3 were closed by C3D-HCWA-POLY, but a later undo rolled that back. Currently holds a Site + ParcelSegment + one 20.2 ft line — re-verify closure.
▾ Symbolisation 1
- ○Point features drawn as Inserts using HCWA standard symbolsAll still raw Circles: 10 manholes, 12 water/hydrant. HCWA requires blocks for Water Vault, Water Valve, Fire Hydrant, Sewer Manhole and Water Meter. Request the HCWA template/seed file — they supply it on request, which makes this a swap rather than hand-building.
▾ Annotations 4
- ✓All required text is single-line text0 MText remaining on HCWA layers (verified)
- ✓Non-standard pipe annotated4"SL, 6"SL, 8" WL, 2" PVC, 1" BWL, 6" PVC stub all labelled
- ○Addresses / lot numbers as number data type (no #, -, ft, ", ')ADDRESS_TEXT empty
- ~Polygon annotation bounded by the polygon it annotatesproject name must sit inside PROJECT_BOUNDARY, which doesn't exist yet
▾ File naming & delivery 5
- !Name matches the project, no blank spaces, underscores only'CSTORE WATER ABS-260612_SHEET.dwg' has spaces. Suggested: East_Lake_Pkwy_C_Store_YYMMDD.dwg
- ○Filename contains revision date in YYMMDD formatmissing
- ✓Delivered in DWG formatyes
- ✓File under 20 MByes
- ~Delivery labelled with file name, company, contact, phonetitle block has SAWHNEY AND ASSOCIATES, 523 Hastings Way Jonesboro GA 30238, (678) 478-6857 — confirm this accompanies the delivery
Not part of this submission
HCWA is a water & sewer authority — these have no layer in the standard. Keep for the client deliverable, exclude from the HCWA package.
- Storm — V-STRM-STRC (9), V-STRM-TEXT (20)
- Grease traps — V-GREASE (8), SS-GREASE (4), incl. the 1500 gal traps + oil/water separator
- RPZ backflow preventer — V-WATR-STRC (1)
- Back-of-curb (TBC) — SS-V-ROAD-CURB (6). HCWA's EOP is explicitly 'not back of curb'.
- Striping / curb shots — SS-FRZ (58)